TY - GEN
T1 - Electric strength of gaseous and liquefied C4-fluoronitrile
AU - Wang, Zi
AU - Kindersberger, Josef
N1 - Publisher Copyright:
© VDE VERLAG GMBH ∙ Berlin ∙ Offenbach
PY - 2021
Y1 - 2021
N2 - For gas-insulated switchgear, an ecologically friendly candidate could be C4-Fluoronitrile (C4-FN), used in gas mixtures, e.g. with CO2. Because of the relatively high dew-point of C4-FN, liquefaction of insulating gas could occur at very low operating temperature. Hence, electric strength and discharge behavior of liquid phase of the insulating gas C4-FN need to be studied. Breakdown voltage and average breakdown field strength are measured by using a hemispherical electrode arrangement according to IEC 60156. Breakdown tests with 50-Hz-AC-voltage are carried out at gas pressures from 0.1 MPa to 0.25 MPa, and with liquefied C4-FN at 20 °C at different gap distances from 1 mm to 5 mm.
AB - For gas-insulated switchgear, an ecologically friendly candidate could be C4-Fluoronitrile (C4-FN), used in gas mixtures, e.g. with CO2. Because of the relatively high dew-point of C4-FN, liquefaction of insulating gas could occur at very low operating temperature. Hence, electric strength and discharge behavior of liquid phase of the insulating gas C4-FN need to be studied. Breakdown voltage and average breakdown field strength are measured by using a hemispherical electrode arrangement according to IEC 60156. Breakdown tests with 50-Hz-AC-voltage are carried out at gas pressures from 0.1 MPa to 0.25 MPa, and with liquefied C4-FN at 20 °C at different gap distances from 1 mm to 5 mm.
UR - http://www.scopus.com/inward/record.url?scp=85101663677&partnerID=8YFLogxK
M3 - Conference contribution
AN - SCOPUS:85101663677
T3 - VDE High Voltage Technology
SP - 188
EP - 193
BT - VDE High Voltage Technology
PB - VDE VERLAG GMBH
T2 - VDE High Voltage Technology 2020
Y2 - 9 November 2020 through 11 November 2020