TY - JOUR
T1 - Breakage of curved copper wires caused by high impulse current of lightning
AU - Hu, Xiaobo
AU - Inaba, Tsuginori
AU - Kindersberger, Josef
PY - 2009
Y1 - 2009
N2 - In past studies, after thin straight copper wires of 0.1 mmφ were exposed to an impulse current, their temperature rose; they melted according to the specific pre-arcing Joule integral in an adiabatic state. However, in this study, we confirmed that thick straight copper wires of 1 mmφ and over it were broken in a solid state before melting The effect of physical damage on copper wire performance was confirmed. The test data suggest that ohmic heating is the main reason for thin (less than 1 mmφ) copper wire breakage in the experiments. However, the magnetic force and skin effect are primarily responsible for breaking thick copper wires rather than thermal failure, as previously thought. And the thicker the copper wires diameter was, the more noticeable the magnetic force and skin effect were. Then the impulse current was impressed through curved copper wires from 0.3 mmφ to 2.0 mmφ. Because of different breakage mechanism for thin and thick copper wires, the current-carrying capability of thin curved copper wires did not change comparing to that of straight ones. However, the current-carrying capability of thick copper wires greatly decreased when they were curved.
AB - In past studies, after thin straight copper wires of 0.1 mmφ were exposed to an impulse current, their temperature rose; they melted according to the specific pre-arcing Joule integral in an adiabatic state. However, in this study, we confirmed that thick straight copper wires of 1 mmφ and over it were broken in a solid state before melting The effect of physical damage on copper wire performance was confirmed. The test data suggest that ohmic heating is the main reason for thin (less than 1 mmφ) copper wire breakage in the experiments. However, the magnetic force and skin effect are primarily responsible for breaking thick copper wires rather than thermal failure, as previously thought. And the thicker the copper wires diameter was, the more noticeable the magnetic force and skin effect were. Then the impulse current was impressed through curved copper wires from 0.3 mmφ to 2.0 mmφ. Because of different breakage mechanism for thin and thick copper wires, the current-carrying capability of thin curved copper wires did not change comparing to that of straight ones. However, the current-carrying capability of thick copper wires greatly decreased when they were curved.
KW - Breakage mechanism
KW - Copper wires
KW - Lightning impulse current
UR - http://www.scopus.com/inward/record.url?scp=73849092919&partnerID=8YFLogxK
U2 - 10.1541/ieejpes.129.309
DO - 10.1541/ieejpes.129.309
M3 - Article
AN - SCOPUS:73849092919
SN - 0385-4213
VL - 129
SP - 309-314+7
JO - IEEJ Transactions on Power and Energy
JF - IEEJ Transactions on Power and Energy
IS - 2
ER -