Abstract
The measurement results of a field test in an isolated network show that the quasi-stationary load-frequency dependence in small isolated grids can be more pronounced than in large interconnected systems. In a droop-based control strategy of the power plants, the load-frequency dependence has an influence on the steady-state operating point. Therefore, a methodology for the determination of frequency-dependent characteristics of loads is presented. In the examined network, another effect occurs which is considered in this study. Transient frequency deviations have a relevant impact on the consumption of reactive power caused by transformers.
Originalsprache | Englisch |
---|---|
Seiten (von - bis) | 1031-1034 |
Seitenumfang | 4 |
Fachzeitschrift | CIRED - Open Access Proceedings Journal |
Jahrgang | 2017 |
Ausgabenummer | 1 |
DOIs | |
Publikationsstatus | Veröffentlicht - 1 Okt. 2017 |
Veranstaltung | 24th International Conference and Exhibition on Electricity Distribution, CIRED 2017 - Glasgow, Großbritannien/Vereinigtes Königreich Dauer: 12 Juni 2017 → 15 Juni 2017 |